The generator of marine motor should operate continuously under full load under the following conditions. The ambient temperature (air) is less than 40 degrees, and the ventilation is good.
Electrical performance of marine motor:
(1) the steady state voltage regulation rate is less than 1%;
(2) transient voltage regulation rate +20%, - 15% (60%In, COSO = 0.4 lag)
(3) no load voltage regulation range (90%-110%) Un
(4) the sinusoidal distortion rate of the voltage waveform of the no-load line is less than 5%
(5) direct starting no load three phase quadrupole squirrel cage motor meets the following table:
Generator power Pn starting motor capacity
40kW and below 0.7Pn
50, 64, 75kW 30 kW
90, 100, 120 kW 55 kW
150, 200, 250 kW 75 kW
320 kW and above 110 kW